Compare material costs for single large conductors vs. parallel smaller runs.
Based on NEC Tables 310.15(B) & 310.16 · 75°C · Copper THWN · EMT Conduit
| Conductor | 600 kcmil |
| Ampacity (per run) | 420A |
| Total ampacity | 420A |
| Conductors/conduit | 4 |
| Conduit runs | 1× 3" EMT |
| Wire (752 lbs Cu) | $4,136.00 |
| Conduit | $850.00 |
| Terminations (8) | $96.00 |
| Conductor | 3/0 AWG |
| Ampacity (per run) | 200A |
| Total ampacity | 400A |
| Conductors/conduit | 4 |
| Conduit runs | 2× 1½" EMT |
| Wire (408 lbs Cu) | $2,244.00 |
| Conduit | $600.00 |
| Terminations (16) | $192.00 |
| Conductor | 1/0 AWG |
| Ampacity (per run) | 150A |
| Total ampacity | 450A |
| Conductors/conduit | 4 |
| Conduit runs | 3× 1¼" EMT |
| Wire (386 lbs Cu) | $2,125.20 |
| Conduit | $750.00 |
| Terminations (24) | $288.00 |
| Conductor | 1/0 AWG |
| Ampacity (per run) | 150A |
| Total ampacity | 600A |
| Conductors/conduit | 4 |
| Conduit runs | 4× 1¼" EMT |
| Wire (515 lbs Cu) | $2,833.60 |
| Conduit | $1,000.00 |
| Terminations (32) | $384.00 |
This tool is provided by PowerTree Inc. for informational and educational purposes only. It does not constitute professional engineering advice. PowerTree Inc., its employees, agents, and affiliates assume no responsibility or liability for any errors, omissions, or outcomes resulting from the use of this tool. All calculations are approximate and must be independently verified by a licensed professional engineer or electrician before being used in any design, construction, or purchasing decision. By using this tool, you agree that PowerTree Inc. shall not be held liable for any direct, indirect, incidental, or consequential damages arising from its use.
Parallel conductors are typically more cost-effective when the required ampacity exceeds 300–400A. At higher amperages, the cost per amp of large single conductors (500 kcmil and above) increases disproportionately due to copper weight and conduit size. Running two or more smaller parallel conductors can reduce material cost, ease installation, and offer more flexibility in conduit routing.
(USA) NEC Section 310.10(G) & (Canada) CSA CEC Rule 12-108(1) both require that parallel conductors be 1/0 AWG or larger, be the same length, material, size, insulation type, and termination method, and be arranged to ensure equal distribution of current. Each phase, neutral, and equipment grounding conductor must have a corresponding conductor in each parallel set.
No. This estimator focuses on material and termination costs only. Voltage drop calculations depend on conductor length, load type, power factor, and other variables. You should perform a separate voltage drop analysis, especially on longer runs, to ensure compliance with NEC recommendations (typically 3% for branch circuits and 5% total).
Copper is the most expensive raw material in electrical conductors. Larger conductors use exponentially more copper per foot — for example, a 500 kcmil conductor weighs roughly 5× more per foot than a 1/0 AWG conductor. When copper prices are high, the cost advantage of parallel smaller conductors becomes more pronounced.
The estimates are approximations intended for preliminary budgeting and comparison purposes. Actual costs vary based on wire manufacturer, insulation type, regional pricing, contractor labor rates, conduit fittings, and market conditions. Always obtain actual supplier quotes for final project budgeting.